The study adopted a 20-foot long container to simulate the situation inside a turbine cabin. Water mist sprays were installed internally and used to perform fire extinguishing tests. Under these different scenarios, several operating factors were adjusted with the results of each adjustment subsequently measured. The operating factors studied included: operating pressures, foam concentrations, cabin opening issues, and obstacles. Each of the factors was compared with the others so as to find out which combinations would be most suitable for a water mist spray system installed inside a wind turbine cabin. The presence of obstructions hinders the direct impact of the mist spray on the fire source and in average an additional 2 to 3 minutes is required to put out the fire. This study found that the effect of the foam-water ratio is linear. Regardless of the scenario, the optimum mixture ratio is 3%. The line graph shows that the most unsuitable aqueous film-forming mixture ratio is 6%. This experiment found that the main fire extinguishing mechanism of water mist spray is the cooling of a large area via water droplets. This system is very effective in bringing down the temperature. The addition of foam in water mist spray, however, impaired the effectiveness of the cooling effect although the fire control mechanism via emulsification markedly reduced the time required to put out the fire. The increase in foam magnification will considerably enhance the fire extinguishing efficiency.