This paper presents the control of the active filter by Duty Cycle Modulation (DCM) for the harmonic pollution control of a three-phase electrical system. Several research works have preceded this work, but most of them deal with the control by pulse-width modulation and the differences lie around the THD reduction performance, the quality of the wave obtained, the simplicity of the scheme and the cost of the control. For this purpose, we propose a very innovative approach to active filter control which aims at reducing the current THD at a lower rate than pulse-width modulation techniques improving at the same time the wave quality with a more simplified control scheme. First we present the schematic diagram of the active filter, then we present the design of the control of this active filter based on the real and imaginary instantaneous power method which uses the algebraic “Clark” transformation. The Duty Cycle Modulation controller is used to obtain the required control commands to be injected to the inverter. We then developed a simulink model of the active filter to validate this study. The simulations were performed in the Matlab/Simulink environment. The results obtained show a significant improvement on the harmonic current control techniques for the THD of 1.02% which was 26.25%, the elimination of noise in the signal and the simplicity of the control with an easier implementation than the pulse width modulation (PWM) make the Duty Cycle Modulation (DCM) control a very promising tool.